A surveillance network that survives its first storm is not the one with the most expensive cameras — it is the one where the installer thought about where energy enters. Lightning is only part of it: most field failures blamed on "a strike" are actually induced surges on the copper data pairs, or a floating earth that turns a small transient into a large one. This note covers the entry points, the devices that clamp them, and the earthing detail that decides whether those devices do anything at all.
A surge protective device does not stop the surge. It conducts it to earth for a few microseconds and clamps the voltage the equipment sees to a level the equipment can survive. That has two consequences people miss: the SPD must have somewhere to send the energy, and the clamp level must be below what the port can take.
| Device | Where it sits | What it protects | Typical rating to ask for |
|---|---|---|---|
| Type 2 AC SPD | distribution board feeding cabinets | switch, NVR, PoE budget supply | Imax 20–40 kA (8/20 µs), Up ≤ 1.5 kV |
| Type 3 AC SPD | local socket / DIN rail in cabinet | single switch, camera PSU | Imax 5–10 kA, Up ≤ 1.0 kV |
| Data-line SPD (RJ45) | at the outdoor camera end and at the switch end | PHY, PoE controller | IEC 61000-4-5, 6 kV / 3 kA per pair |
| PoE in-line protector | in series on the outdoor run | both power and data pairs | clamp below 60 V, insertion loss < 1 dB |
The important number is the clamp voltage, not the joule rating on the box. For a PoE port the protector must clamp below the PHY's absolute maximum while never clamping so low that it interferes with the 57 V PoE negotiation. That is why a generic data-line protector is a poor substitute for a PoE-rated one.
An SPD with no return path is a decoration. Outdoor cabinets should be bonded to the same earth as the building's earthing system, ideally at one point, and the shield or drain wire should be terminated at the cabinet rather than floated. Two separately earthed points — say the pole and the building — are how a modest potential difference becomes a destructive current.
Our industrial switch range is built for cabinets that sit outside the building envelope, and the PoE switch range covers the indoor distribution side. For long outdoor links, an optical converter replaces the copper run entirely.
| Line item | Why it is there |
|---|---|
| Type 2 SPD at the cabinet feed | takes the bulk of the AC transient |
| Type 3 SPD or PoE protector per outdoor run | clamps what reaches the port |
| Bonded cabinet with single earth reference | gives the SPD a return path |
| Spare PoE ports sized to the cabinet | turns a failure into a re-patch |
| Surge rating stated on the switch datasheet | separates real industrial hardware from relabelled office gear |
Tell us the site: how many outdoor runs, whether the cabinets are earthed, and the distance between buildings. We will return a protection scheme with the port count that fits. Ask for a quote.
Every camera on an outdoor copper run should have protection at the camera end, and the switch side should be protected as well. Cameras inside the same building on short indoor runs are usually fine without it.
No. A direct strike is beyond what surge devices are rated for; lightning protection is a separate system (air terminals, bonding, earthing). SPDs handle the induced surges that cause the majority of equipment failures.
Fibre. It removes the electrical path instead of clamping it, so there is nothing left to protect and no earth reference to get wrong.
Almost always an earthing problem or a protector installed on one end only. Check that the cabinet is bonded to the same earth as the building and that both ends of the run are protected.